RECOVERY - RECYCLING
COMPACT AND
LIGHT DESIGN
INCLUDED
COMPLIANCE
NF EN35421
R1234ze
ISO 11650
CE N.1005 2009
IEC60335-2-104
UE-517/2014
RECOVER
RECYCLE
REUSE
INCLUDED
R32
CERAMIC CYLINDER
WITH CARBON
FIBER SEAL
Integrated distillation system
EASYREC-3R
High performance recovery and recycling unit for
CFC, HCFC, HFC and HFO (included R32 and R1234ze)
• High performances thanks to the powerful 1 HP compressor and to the
higher capacity condenser.
• Very compact and light design with integrated distiller.
• Exclusive distillation device with liquid refrigerant flow check which:
- allows to separate oil/impurities/dyes very efficiently.
- optimizes the compressor’s operating conditions.
• Ceramic cylinders with carbon fibre seal for superior reliability.
• Large, intuitive heavy-duty digital display that supports the user in the
recovery and recycling phases guiding him as well with the discharge
procedure of oil/impurities/dye.
• Multiple selectable recovery and recycling modes.
• Automatic stop of the unit at the end of recovery with visual and acoustic
indication.
• Shut-off valves that prevent refrigerant spills.
• Self-evacuation (PURGE) device, which allows to change type of refrigerant easily.
• Safety device for maximum pressure.
• Sight-glass and filters included.
Oil
discharge
High-efficiency heat exchanger
Automatic flow control
Refrigerant
output
Refrigerant
input
Technical features
Refrigerant
Compressor
Operating
temperature
CFC, HCFC, HFC e HFO
(included R32 and R1234ze)
Double piston, dry
0 - 40 oC
Power supply
220 - 240V AC 50 - 60 Hz
Motor power
750W
Maximal current draw
6A
Automatic safety
shut-off
38.5 bar/3850 kPa (558 psi)
Recovery rate
R1234ze-
R134a
R502-
R407C
R404A-R410A-
R507-R32
REGULATION UE-517/2014 AND 2024 UPDATE
Vapour
Liquid (recovery-recycling)
29 kg/h
32 kg/h
30 kg/h
34 kg/h
33 kg/h
35 kg/h
Liquid (recovery)
214 kg/h
340 kg/h
380 kg/h
Code
Model
Dimensions with pack
Weight with pack
13001029
EASYREC-3R
380 x 360 x 250 mm
13,90 kg
Push-pull
372 kg/h
474 kg/h
502 kg/h
ARTICLE 13 – CONTROL OF USE
From 1
st
January 2020, the use of fluorinated greenhouse gases, with a global warming potential of 2500 or more, to service or maintain refrigeration equipment
with a charge size of 40 tonnes of CO2 equivalent or more, is prohibited. From 1
st
January 2025, it is planned to extend this ban to all refrigeration systems
regardless of the refrigerant charge.
In accordance with Article 13 Paragraph 3 Subparagraph b), until 1
st
January 2030 recycled fluorinated greenhouse gases with a global warming potential of 2500 or
more contained in refrigeration equipment with a load size equal to or greater than 40 tonnes of CO2 equivalent may be used for the maintenance or repair of existing
refrigeration equipment, provided they have been recovered from such equipment.
Such recycled gases may only be used by the undertaking which carried out their recovery as part of maintenance or servicing or the undertaking for which the recovery was
carried out as part of maintenance or servicing. Regulation (EU) No. 517/2014 Article 2 point 15 and the new Regulation Article 3 point 12 define ‘recycling’ as the re-use of a
recovered fluorinated greenhouse gas after a basic cleaning process.