RECOVERY - RECYCLING

RECOVERY-RECYCLING UNIT

RECOVER

RECYCLE

REUSE

INCLUDED

R32

INCLUDED

R1234ze

COMPLIANCE

ISO 11650

IEC60335-2-104

NF EN35421

CE N.1005 2009

UE-517/2014

EASYREC-1R

Recovery and recycling unit suitable for

CFC, HCFC, HFC and HFO (included R32 and R1234ze)

• Compact design with integrated distiller.

• Distillation device with liquid refrigerant flow check, which allows to

separate oil/impurities/dyes very efficiently.

• Self-evacuation system (PURGE) which allows to change the type of re-

frigerant easily.

• Automatic stop of the unit when there is no refrigerant available in the

system.

• Signal LED (green/cycle performed successfully - red/alarm).

• Safety device for maximum pressure.

• Two cut-off valves to prevent refrigerant discharge.

• “Pulse free” gauges with regulation screw.

• Ceramic cylinder with carbon fiber seal.

• Sight glass and filter included.

• Wide graphics with quick functioning instructions.

Code

Model

Dimensions with pack

13001020 EASYREC-1R 545 x 300 x 395 mm

Technical features

Weight with pack

18,9 kg

CERAMIC CYLINDER

WITH CARBON

FIBER SEAL

REGULATION UE-517/2014 AND 2024 UPDATE

ARTICLE 13 – CONTROL OF USE

From 1

st

January 2020, the use of fluorinated greenhouse gases, with a global

warming potential of 2500 or more, to service or maintain refrigeration equipment

with a charge size of 40 tonnes of CO2 equivalent or more, is prohibited. From 1

st

January 2025, it is planned to extend this ban to all refrigeration systems regardless

of the refrigerant charge.

In accordance with Article 13 Paragraph 3 Subparagraph b), until 1

st

January 2030

recycled fluorinated greenhouse gases with a global warming potential of 2500 or more

contained in refrigeration equipment with a load size equal to or greater than 40 tonnes of

CO2 equivalent may be used for the maintenance or repair of existing refrigeration

equipment, provided they have been recovered from such equipment.

Such recycled gases may only be used by the undertaking which carried out their recovery

as part of maintenance or servicing or the undertaking for which the recovery was carried

out as part of maintenance or servicing. Regulation (EU) No. 517/2014 Article 2 point 15

and the new Regulation Article 3 point 12 define ‘recycling’ as the re-use of a recovered

fluorinated greenhouse gas after a basic cleaning process.

Refrigerant

Power supply

Motor power

Maximal current draw

Compressor

Automatic safety

shut-off

Operating

temperature

Recovery rate

Vapour

Liquid (recovery)

Liquid (recovery-recycling)

Push-pull

CFC, HCFC, HFC and HFO

(included R32 and R1234ze)

220 - 240V AC 50 - 60 Hz

550W

4A

Piston-type and oil less

38.5 bar/3850 kPa (558 psi)

0 - 40 oC

i

Integrated distillation system

R1234ze-

R134a

14 kg/h

96 kg/h

16 kg/h

276 kg/h

R502-

R407C

15 kg/h

108 kg/h

17 kg/h

336 kg/h

R404A-R410A-

R507-R32

16 kg/h

132 kg/h

18 kg/h

378 kg/h

Oil

discharge

High-efficiency heat exchanger

Automatic flow control

Refrigerant

output

Refrigerant

input

HIGH heat exchange between “warm” refrigerant

and “cold” refrigerant, that allows to optimize the

distillation procedure

Automatic flow control system

Max filling up control

Distillation device which allows to separate

oil/impurities/dyes very efficiently

16